State rules
Mississippi
The Mississippi State Department of Health drinking-water regulations require every public water supply to adopt a cross-connection control policy no less stringent than the regulation, and no more stringent than Mississippi Code section 41-26-14. When a reduced-pressure principle assembly, double check valve assembly, or pressure vacuum breaker is installed to protect the public system, required inspection and testing are performed by a person licensed as a Certified Tester by the Department. The Department develops and administers the certification test at the end of each approved training program. A written score of at least 70 percent and a successful performance test on the three assembly types are required. Certification expires three years from the date issued.
Checked against official sources on October 11, 2026. Rules and links change; confirm with the office listed before you act.
- Drinking-water agency
- The Mississippi State Department of Health licenses Certified Testers and requires public water supplies to enforce a cross-connection program.
- Who may test an assembly
- A Certified Tester licensed by the Department performs required inspection and testing of the assemblies named in the rule.
- Official program page
- Official page →
The regulations separate hazards. A high-hazard cross-connection involves material dangerous to health under pressure or negative pressure, and it is removed by an air gap or protected by a Department-recommended assembly. Irrigation that injects or stores lawn chemicals, or that connects to wastewater, is high hazard. Professionally installed irrigation that does none of those things is on the very-low-risk list and is not required to have a preventer. Certain pools, drinking fountains, and chemical-free fire sprinklers are on that list too. The water system makes the hazard call, subject to Department review.
Reduced-pressure principle assemblies and pressure vacuum breakers are inspected and tested at least once a year by a Certified Tester, and every covered assembly is tested after installation and before the customer uses it. The tester gives the owner and the water system a written report on a Department form. Tester and system keep results at least five years. A reduced-pressure or pressure-vacuum-breaker assembly that fails must be repaired or replaced within thirty days. A double check that fails must be repaired or replaced within ninety days. Reduced-pressure and double-check assemblies shall not be located in a pit below ground level.
Training must be submitted to the Department at least 45 days before the course. The Department may, solely at its discretion and without testing, certify a tester who already holds certification from a nationally recognized program. The rule does not name that program. Recertification is by an examination the Department develops. Carbonated-beverage dispensers have a narrow exception if the connection is protected by a device conforming to ASSE 1022 or by an air gap, and if carbon dioxide does not affect the device and downstream piping. That ASSE number is a device standard in the beverage rule, not the tester license.
Official resources in Mississippi
Contains the cross-connection program rules and the Certified Tester licensing rules.
Statute section on high-hazard and low-hazard cross-connections and the very-low-risk category.
Federal educational manual. It does not replace the Department’s Certified Tester license.
Key facts for Mississippi
- Required tests of reduced-pressure, double-check, and pressure-vacuum-breaker assemblies are performed by a Department-licensed Certified Tester.
- Certification requires at least 70 percent on the written exam and a successful performance test on all three assembly types.
- Certification expires three years from the date issued.
- Reduced-pressure assemblies and pressure vacuum breakers are tested at least annually.
- Failed reduced-pressure and pressure-vacuum-breaker assemblies are repaired or replaced within 30 days; failed double checks within 90 days.
- Professionally installed lawn irrigation that does not inject or store chemicals and is not tied to wastewater is listed as very low risk and is not required to have a backflow preventer.
What to do next
- Ask for the Department Certified Tester license, not only a course flyer.
- Tell the tester if the irrigation system injects chemicals; that is high hazard under the rule.
- If a test fails, note whether the assembly is a double check, because the repair window is longer.
- Do not put a reduced-pressure or double-check assembly in a below-ground pit.
Looking for your city or county in Mississippi?
We haven't found official program-level pages for Mississippi we can verify yet, so we don't show local numbers here rather than guess. Here's what to use instead, in order:
- General Start with the statewide information above. It applies across Mississippi, but cities and counties can add their own steps, fees or deadlines.
- Call to confirm Ask the official office. They have the current local rule, fee and form.Mississippi State Department of Health public water supply regulations
Website →Phone not shown: use the contact page on the official website above.Your city or county office: Local governments →Not sure who handles it locally? USAGov's free help line, 1-844-872-4681, or the Mississippi page on USA.gov can point you to the right office. - Know the current info? Tell us and include a link to the official page. We check every tip before it goes up.
Helpful guides
- What a backflow test is
- Who is allowed to test a backflow assembly
- Why utilities require annual backflow testing
- Tester and cross-connection specialist